Article image Water Supply Systems Design: Cross-Connection Control in Water Supply

17.8. Water Supply Systems Design: Cross-Connection Control in Water Supply

Page 40 | Listen in audio

Cross-connection control in water supply systems is a critical aspect of plumbing design that ensures the safety and integrity of potable water systems. A cross-connection is any actual or potential connection between a potable water system and any source of contamination or pollution. The primary goal of cross-connection control is to prevent backflow, which is the undesirable reversal of water flow that can introduce contaminants into the clean water supply.

Backflow can occur in two ways: backpressure and backsiphonage. Backpressure occurs when the pressure in the non-potable system exceeds the pressure in the potable system, forcing contaminants into the potable water. Backsiphonage happens when there is a negative pressure in the potable water system, such as during a water main break or heavy water usage, which can draw contaminants into the system.

To effectively control cross-connections, several strategies and devices are employed. These include air gaps, reduced pressure zone (RPZ) assemblies, double check valve assemblies, pressure vacuum breakers, and atmospheric vacuum breakers. Each device has specific applications and limitations, and choosing the right one depends on the level of hazard, system requirements, and local regulations.

Air Gaps

An air gap is the simplest and most reliable method of preventing backflow. It is a physical separation between the potable water outlet and the flood level rim of the receiving vessel. The air gap should be at least twice the diameter of the outlet pipe but never less than one inch. While air gaps are highly effective, they are not always practical for all applications due to space constraints or aesthetic considerations.

Reduced Pressure Zone (RPZ) Assemblies

RPZ assemblies are mechanical devices designed to prevent backflow in high-hazard situations. They consist of two independently acting check valves with a pressure-monitored zone between them. If either check valve fails, the pressure in the zone will drop, causing a relief valve to open and discharge to the atmosphere, thus preventing backflow. RPZ assemblies are commonly used in commercial and industrial applications where the risk of contamination is significant.

Double Check Valve Assemblies

Double check valve assemblies are used in low to medium hazard situations. They consist of two check valves in series, providing redundancy in case one valve fails. While not as robust as RPZ assemblies, double check valve assemblies are suitable for applications where the potential for contamination is lower, such as residential irrigation systems.

Pressure Vacuum Breakers

Pressure vacuum breakers are used to prevent backsiphonage in situations where the supply pressure is greater than atmospheric pressure. They consist of an air inlet valve and a check valve, which open to the atmosphere when pressure drops, preventing siphoning. Pressure vacuum breakers are typically used in irrigation systems and other outdoor water uses.

Atmospheric Vacuum Breakers

Atmospheric vacuum breakers are simple devices used to prevent backsiphonage. They consist of a check valve that opens to the atmosphere when the pressure in the system drops. These devices are typically used in low-hazard applications, such as residential hose bibs and toilet fill valves. However, they are not suitable for continuous pressure applications.

To ensure effective cross-connection control, it is essential to conduct regular inspections and maintenance of backflow prevention devices. This includes testing devices at least annually, as required by many plumbing codes and regulations. Additionally, proper installation is crucial; devices must be installed in accessible locations for testing and maintenance, and in accordance with manufacturer specifications and local codes.

Another critical aspect of cross-connection control is the identification and assessment of potential cross-connections during the design phase of a plumbing system. This involves a thorough understanding of the building's water usage, potential contamination sources, and the classification of hazards. By identifying potential cross-connections early in the design process, appropriate preventive measures can be integrated into the system.

Education and training are also vital components of cross-connection control. Building owners, facility managers, and maintenance personnel should be aware of the importance of backflow prevention and the operation of backflow prevention devices. Training programs and resources should be made available to ensure that those responsible for maintaining plumbing systems have the knowledge and skills to identify and mitigate cross-connections effectively.

Furthermore, collaboration between designers, engineers, and local water authorities is essential to ensure compliance with regulations and standards. Local water authorities often have specific requirements and guidelines for cross-connection control, and working closely with them can help ensure that the plumbing system design meets all necessary safety standards.

In conclusion, cross-connection control is a fundamental component of water supply system design that protects public health by preventing contamination of potable water. By employing a combination of mechanical devices, regular inspections, and thorough planning, the risk of backflow can be effectively managed. Through education, training, and collaboration with local authorities, the integrity of water supply systems can be maintained, ensuring safe and reliable access to clean water for all users.

Now answer the exercise about the content:

What is the primary goal of cross-connection control in water supply systems?

You are right! Congratulations, now go to the next page

You missed! Try again.

Article image Water Supply Systems Design: Water Supply System Redundancy and Reliability

Next page of the Free Ebook:

41Water Supply Systems Design: Water Supply System Redundancy and Reliability

7 minutes

Earn your Certificate for this Course for Free! by downloading the Cursa app and reading the ebook there. Available on Google Play or App Store!

Get it on Google Play Get it on App Store

+ 6.5 million
students

Free and Valid
Certificate with QR Code

48 thousand free
exercises

4.8/5 rating in
app stores

Free courses in
video, audio and text