Free Ebook cover Refrigeration Cycle Fundamentals for Beginners

Refrigeration Cycle Fundamentals for Beginners

New course

10 pages

Refrigeration Cycle Fundamentals: Pressure–Temperature Relationships You Must Read Correctly

Capítulo 3

Estimated reading time: 6 minutes

+ Exercise

Why Pressure Tells You a Temperature (But Not the One You Measured)

In a working vapor-compression system, pressure and saturation temperature are linked for a given refrigerant. A P–T chart (pressure–temperature chart) lets you convert a measured pressure into the saturation temperature—the temperature at which that refrigerant would be boiling/condensing at that pressure.

Key skill: keep two temperatures separate in your mind and on your notepad:

  • Saturation temperature (Tsat): comes from pressure using a P–T chart for the correct refrigerant.
  • Actual line temperature (Tline): measured with a temperature clamp/probe on the tubing.

You compare them to determine:

  • Superheat (typically on the suction/evaporator outlet side): Superheat = Tline − Tsat
  • Subcooling (typically on the liquid/condensing outlet side): Subcooling = Tsat − Tline

Notice the subtraction order changes. That is not a math trick; it reflects what you expect physically: suction vapor should be warmer than its saturation temperature (superheated), and liquid line should be cooler than its saturation temperature (subcooled).

The 4-Step Field Method (Use This Every Time)

Step 1) Measure pressure (and know what kind of pressure it is)

  • Connect your gauge/manifold or digital probes to the correct service port.
  • Read gauge pressure (psig, barg). Most field gauges show gauge pressure, not absolute.
  • Identify whether you are on the low side (suction/evaporator pressure) or high side (discharge/liquid/condensing pressure).

Quick check: If your “low side” reading is higher than your “high side,” you are either on the wrong port, your valves are mis-positioned, or the system is off equalized.

Continue in our app.

You can listen to the audiobook with the screen off, receive a free certificate for this course, and also have access to 5,000 other free online courses.

Or continue reading below...
Download App

Download the app

Step 2) Convert pressure to saturation temperature using a P–T chart

  • Select the correct refrigerant scale (R-410A, R-134a, R-404A, etc.).
  • Convert the measured pressure to Tsat using the chart/app.
  • Write it down as Tsat@measured pressure so you don’t confuse it with a thermometer reading.

Quick check: Many blends have a bubble/dew distinction. For basic superheat/subcooling work, technicians commonly use dew for superheat (evaporating) and bubble for subcooling (condensing). If your tool shows both, pick the one that matches the measurement you’re doing.

Step 3) Measure the actual line temperature at the correct location

  • Superheat measurement location: suction line near the evaporator outlet (or at the suction service valve if that’s your standard procedure), with good clamp contact and insulation over the probe if possible.
  • Subcooling measurement location: liquid line near the condenser outlet (or liquid service valve), again with solid contact and minimal influence from ambient air.

Quick check: A shiny copper line in hot sun can read falsely high if the probe is not insulated. Always aim for good thermal contact and shield from radiant heat.

Step 4) Compare Tsat to Tline to determine superheat or subcooling

Use the correct formula for the side you are on:

  • Superheat (suction): SH = Tline(suction) − Tsat(evap)
  • Subcooling (liquid): SC = Tsat(cond) − Tline(liquid)

Interpretation basics:

  • Positive superheat means vapor is warmer than its boiling point at that pressure (expected).
  • Positive subcooling means liquid is cooler than its condensing point at that pressure (expected).
  • Near-zero or negative values usually indicate a measurement/setup error or an abnormal operating condition that must be verified carefully.

Worked Examples (Realistic Numbers)

These examples focus on the skill: pressure → Tsat, then compare with measured line temperature.

Example 1: Suction superheat on an R-410A comfort cooling system

  • Step 1: Measure suction pressure: 118 psig
  • Step 2: P–T chart (R-410A) gives Tsat ≈ 40°F at 118 psig
  • Step 3: Measure suction line temperature at evaporator outlet: Tline = 52°F
  • Step 4: Superheat = 52 − 40 = 12°F

Meaning: The suction vapor is 12°F above its saturation temperature at that pressure.

Example 2: Liquid subcooling on the same R-410A system

  • Step 1: Measure liquid/high-side pressure: 360 psig
  • Step 2: P–T chart (R-410A) gives Tsat ≈ 110°F at 360 psig
  • Step 3: Measure liquid line temperature leaving condenser: Tline = 98°F
  • Step 4: Subcooling = 110 − 98 = 12°F

Meaning: The liquid is 12°F below its saturation temperature at that pressure (subcooled liquid).

Example 3: R-134a medium-temp system—superheat check

  • Step 1: Suction pressure: 22 psig
  • Step 2: P–T chart (R-134a) gives Tsat ≈ 26°F
  • Step 3: Suction line temperature: Tline = 38°F
  • Step 4: Superheat = 38 − 26 = 12°F

Common mistake check: If you accidentally used an R-410A scale at 22 psig, you’d get a completely different Tsat and your calculated superheat would be meaningless. Always confirm refrigerant selection before trusting the number.

Example 4: R-134a subcooling check with a probe placement error

  • Step 1: High-side pressure: 118 psig
  • Step 2: P–T chart (R-134a) gives Tsat ≈ 95°F
  • Step 3 (bad measurement): Liquid line temperature measured on a section of line near a hot compressor discharge line: Tline = 102°F
  • Step 4: Subcooling = 95 − 102 = −7°F

What to do: Negative subcooling often means you are not actually measuring the liquid line temperature correctly (or you are not on a true liquid column). Re-measure at the condenser outlet/liquid service valve, ensure the line is actually the liquid line, improve probe contact, and insulate the probe. If after correcting measurement technique you still get near-zero/negative subcooling, then you investigate system conditions.

Example 5: Confusing high side and low side (how it shows up in the math)

Suppose you intended to calculate superheat but accidentally used the high-side pressure to find Tsat.

  • Measured suction line temperature: Tline(suction) = 55°F
  • Accidentally used high-side pressure: 350 psig on R-410A → Tsat ≈ 108°F
  • Calculated “superheat”: 55 − 108 = −53°F

Quick diagnosis: A huge negative “superheat” is a red flag. You likely used the wrong pressure (high side instead of suction), the wrong refrigerant scale, or the system is off and equalized. Re-check Step 1 and Step 2.

Mini Checklist: Common Mistakes and Fast Fixes

MistakeWhat you’ll seeFast fix
Wrong refrigerant selected on gauge/appTsat doesn’t make sense for the operating condition; superheat/subcooling looks extremeVerify refrigerant from nameplate/work order; set correct scale before converting pressure
Mixing saturation temperature with actual temperatureWriting down one temperature and forgetting which it is; inconsistent calculationsLabel readings explicitly: Tsat@P and Tline
Using the wrong side pressure (high vs low)Negative or wildly large superheat/subcoolingConfirm hose/probe location; identify suction vs liquid line by temperature and routing
Poor temperature measurement techniqueSubcooling goes negative near hot components; readings change when you touch the probeImprove clamp contact, clean pipe, insulate probe, avoid radiant heat sources
System not stabilizedPressure and temperature readings drift quickly; calculations jump aroundAllow operating conditions to settle before recording final values

Practice Drill (Do This on Paper Before You Touch a System)

For each scenario, write down: P, Tsat, Tline, then compute SH or SC.

  • Scenario A (superheat): R-410A suction pressure 125 psig; Tsat from chart; suction line temp 54°F.
  • Scenario B (subcooling): R-410A liquid pressure 390 psig; Tsat from chart; liquid line temp 101°F.
  • Scenario C (superheat): R-134a suction pressure 18 psig; Tsat from chart; suction line temp 35°F.

When you check your work, focus less on the final number and more on whether you used the correct refrigerant scale, correct side pressure, and correct subtraction order.

Now answer the exercise about the content:

When calculating liquid-line subcooling, which subtraction order correctly compares measured line temperature to saturation temperature from pressure?

You are right! Congratulations, now go to the next page

You missed! Try again.

For subcooling, you compare the condensing saturation temperature (from the measured high-side pressure) to the actual liquid-line temperature: SC = Tsat − Tline. This should be positive when the liquid is cooler than its saturation temperature.

Next chapter

Refrigeration Cycle Fundamentals: The Compressor’s Role and What Changes Across It

Arrow Right Icon
Download the app to earn free Certification and listen to the courses in the background, even with the screen off.