Free Ebook cover Refrigeration Cycle Fundamentals for Beginners

Refrigeration Cycle Fundamentals for Beginners

New course

10 pages

Refrigeration Cycle Fundamentals: Condenser Heat Rejection and Subcooling

Capítulo 5

Estimated reading time: 7 minutes

+ Exercise

What the Condenser Must Accomplish

The condenser’s job is to reject heat from the high-pressure refrigerant leaving the compressor so that it becomes a stable liquid supply for the metering device. In practice, the condenser does this in three distinct heat-rejection zones that often occur in series along the coil: (1) desuperheating, (2) condensing at saturation, and (3) liquid subcooling. Thinking in zones helps you diagnose what the system is doing using only pressure and temperature measurements.

Three-Zone Condenser Diagram (Conceptual)

Below is a simplified “flow-through” diagram of a typical air-cooled condenser. The refrigerant enters as a hot, high-pressure vapor and leaves as a high-pressure liquid. Air (or water) carries the rejected heat away.

Refrigerant flow direction  ─────────────────────────────────────────>  (to liquid line / metering device)

  Inlet (from compressor)                                              Outlet (to liquid line)
  Hot, high-pressure vapor                                              High-pressure liquid

  ┌───────────────────────┬──────────────────────────┬──────────────────────────┐
  │ Zone 1: Desuperheat    │ Zone 2: Condense (sat.) │ Zone 3: Subcool liquid    │
  │ Superheated vapor      │ Two-phase mixture       │ 100% liquid below sat.    │
  │ Temperature drops      │ Temp ~ constant         │ Temperature drops further │
  │ to saturation temp     │ while vapor becomes     │ below condensing temp     │
  │ at that pressure       │ liquid                  │ (subcooling)              │
  └───────────────────────┴──────────────────────────┴──────────────────────────┘n
Heat rejected to ambient air/water across all zones (sensible + latent + sensible)

Zone 1: Desuperheating (Sensible Heat Removal)

At the condenser inlet, the refrigerant is typically superheated vapor. In the desuperheating zone, the condenser removes sensible heat: the vapor temperature drops down to the saturation (condensing) temperature that corresponds to the high-side pressure. No phase change occurs yet; it is still vapor, just cooler vapor.

  • What you’d observe: Refrigerant temperature decreases along the coil; pressure is roughly steady (small drop due to friction).
  • Why it matters: The refrigerant must reach saturation before it can begin condensing (phase change).

Zone 2: Condensing at Saturation (Latent Heat Removal)

Once the refrigerant reaches saturation at the prevailing high-side pressure, it begins to condense. In this zone, the condenser removes mostly latent heat as vapor changes to liquid. The key idea is that during phase change at a given pressure, the refrigerant temperature stays approximately constant at the saturation (condensing) temperature (again, ignoring small pressure drops).

  • What you’d observe: A large amount of heat is rejected with little change in refrigerant temperature; the refrigerant inside is a two-phase mixture that becomes progressively more liquid.
  • Why it matters: This is where the “bulk” of heat rejection happens.

Zone 3: Liquid Subcooling (Sensible Heat Removal)

After all vapor has condensed, the refrigerant is 100% liquid. If the condenser continues to remove heat beyond the point of complete condensation, the liquid temperature drops below the saturation (condensing) temperature at that pressure. That temperature difference is subcooling.

Continue in our app.

You can listen to the audiobook with the screen off, receive a free certificate for this course, and also have access to 5,000 other free online courses.

Or continue reading below...
Download App

Download the app

  • What you’d observe: Liquid line temperature is lower than the condensing saturation temperature.
  • Why it matters: Subcooling indicates the liquid is not “on the verge” of flashing into vapor. This improves the quality of liquid delivered to the metering device.

How to Calculate Subcooling (Guided Field Example)

This example uses the most common field approach: measure high-side pressure, convert it to a saturation (condensing) temperature using a PT chart/app for the refrigerant, then compare that to the measured liquid line temperature.

Tools and Measurements You Need

  • High-side pressure at the condenser outlet or liquid line service port (psig or kPa gauge).
  • Liquid line temperature measured on the liquid line near the condenser outlet (use a clamp thermocouple/thermistor; insulate the probe from ambient air).
  • Refrigerant type (e.g., R-410A, R-134a, R-404A, etc.) so you use the correct PT relationship.

Step-by-Step Procedure

  1. Stabilize operating conditions. Let the system run until pressures and temperatures are steady. Rapidly changing load or airflow will make subcooling bounce.

  2. Record the measured high-side pressure. Example: High-side pressure = 260 psig (refrigerant: R-410A).

  3. Convert pressure to condensing (saturation) temperature. Using an R-410A PT chart/app, find the saturation temperature at 260 psig. Example result: T_sat,cond ≈ 85°F. (Your exact value depends on the PT source and whether it uses dew/bubble conventions; for subcooling you typically use the liquid/bubble saturation reference.)

  4. Measure the liquid line temperature. Place the temperature clamp on the liquid line leaving the condenser (or at the receiver outlet if present). Insulate the sensor. Example: T_liquid = 78°F.

  5. Calculate subcooling.

    Subcooling = T_sat,cond − T_liquid

    Using the example values:

    Subcooling = 85°F − 78°F = 7°F

Interpreting the Number: What Subcooling Indicates

Subcooling is a statement about liquid quality in the liquid line. If the liquid temperature is below the saturation temperature at that same pressure, the refrigerant is confidently in the liquid region (not a liquid-vapor mix). That means the liquid line is less likely to contain “flash gas” (vapor bubbles formed by pressure drop or heat gain).

  • Higher subcooling (within design intent) generally means a more stable, fully liquid feed to the metering device.
  • Very low or zero subcooling means the liquid is at (or very near) saturation; small pressure drops in the liquid line, filter-drier, solenoid, or distributor can cause some of it to flash into vapor before the metering device.

Why Stable Subcooled Liquid Helps Metering Performance

Metering Devices Expect Liquid, Not a Liquid/Vapor Mix

Most metering devices are designed to control flow based on a pressure drop and a predictable inlet condition. A stable, subcooled liquid inlet helps the device behave consistently.

  • TXV/TEV systems: A TXV tries to regulate evaporator superheat by modulating flow. If vapor bubbles enter the valve (flash gas), the valve can become “starved” of liquid, reducing effective mass flow and making control less stable.
  • Fixed orifice/capillary systems: These devices have no active control. If the inlet is partly vapor, the mass flow rate drops and the evaporator can be underfed, especially under higher load conditions.

Subcooling as “Margin” Against Flashing

As liquid travels from the condenser to the metering device, it experiences:

  • Pressure drops (friction through tubing, filter-drier, valves, fittings), which lower saturation temperature.
  • Heat gain from the ambient around the liquid line, which raises liquid temperature.

Subcooling provides a temperature cushion so that even with some pressure drop and heat gain, the refrigerant remains liquid until it reaches the metering device. In other words, subcooling improves the probability that the metering device sees a solid column of liquid rather than a frothy mixture.

Practical Notes for Accurate Subcooling Measurements

  • Measure temperature at the right spot: As close as practical to the condenser outlet (or receiver outlet). Farther downstream increases the chance of heat gain affecting the reading.
  • Insulate the temperature probe: Air blowing across the line can skew the clamp reading away from true line temperature.
  • Use the correct saturation reference: For blends, ensure you’re using the appropriate bubble (liquid) saturation temperature when calculating subcooling.
  • Expect small pressure drops: The pressure at your gauge port may not be exactly the same as pressure at the condenser outlet; keep measurement locations consistent for repeatability.

Quick Reference Table: What Each Zone “Looks Like” in Measurements

Condenser ZoneRefrigerant ConditionMain Heat Type RemovedTypical Temperature BehaviorDiagnostic Hint
DesuperheatingSuperheated vaporSensibleTemperature drops toward saturationLarge inlet-to-sat temperature difference indicates significant superheat entering condenser
Condensing at saturationTwo-phase (vapor + liquid)LatentTemperature ~ constant at T_sat for that pressureMost of the coil’s heat rejection occurs here
SubcoolingLiquidSensibleLiquid temperature drops below T_satSubcooling = T_sat − T_liquid; indicates liquid stability to the metering device

Now answer the exercise about the content:

In an air-cooled condenser, what does measured subcooling indicate about the refrigerant leaving the condenser and why is it helpful for the metering device?

You are right! Congratulations, now go to the next page

You missed! Try again.

Subcooling is T_sat,cond − T_liquid. If the liquid line temperature is below saturation at the same pressure, the refrigerant is solidly liquid. This temperature cushion helps prevent flash gas from pressure drops or heat gain, supporting stable metering.

Next chapter

Refrigeration Cycle Fundamentals: Metering Devices and the Expansion Process

Arrow Right Icon
Download the app to earn free Certification and listen to the courses in the background, even with the screen off.