Purpose and mindset: one workflow for many motor-driven loads
Fans, pumps, compressors, and HVAC motors fail in repeatable ways, but the safest troubleshooting is consistent regardless of the load type. Use a fixed sequence that (a) confirms the complaint, (b) proves whether the issue is supply/control/motor/load, and (c) captures measurements you can defend later. The goal is not to “try parts,” but to isolate the fault with the least exposure to energized work.
1) Pre-checks (before meters and megohmmeters)
1.1 Verify the complaint (what exactly is wrong?)
- Define the symptom: won’t start, starts then trips, runs but low airflow/flow, noisy/vibrating, overheats, intermittently stops, breaker trips, overload trips, control fuse blows.
- Confirm operating conditions: ambient temperature, recent maintenance, filter status (HVAC), valve positions (pumps), damper positions (fans), head pressure conditions (compressors), recent power events.
- Reproduce safely: if possible, observe one start/stop cycle from a safe position with guards in place. Note any delay, chatter, or abnormal sound.
1.2 Review documentation: nameplate/control diagram (without re-learning basics)
- Identify the exact motor and starter: voltage, phase, full-load current (FLA), service factor if used on site, wiring diagram in the control panel door, and any interlocks (pressure switches, float switches, freezestats, airflow switches).
- Confirm the control scheme: two-wire (maintained) vs three-wire (start/stop), HOA switch, BAS/thermostat call, safety chain devices, and any permissives.
- Know what “normal” should be: expected line voltage range, expected control voltage, expected running current range for the load.
1.3 Visual inspection (de-energized whenever possible)
- Motor and load: burnt smell, discoloration, oil leakage, damaged fan blades, blocked intake/exhaust, iced coil, clogged strainers, seized pump, loose mounting bolts.
- Wiring and terminations: overheated lugs, insulation damage, loose grounds, evidence of arcing, water ingress, conduit fill issues, rubbing on rotating parts.
- Controls: contactor tips pitted/welded, overload reset popped, loose control wires, blown control fuse, cracked relays, signs of overheating in the panel.
1.4 Lockout/Tagout (LOTO) and stored energy checklist
Before opening guards, pulling leads, or touching terminals, apply LOTO and verify absence of voltage. Many “motor” incidents occur during troubleshooting, not normal operation.
- Identify all energy sources: main feeder, control transformer secondary, separate control feed, VFD/soft starter bypass feeds, generator/ATS, UPS controls, capacitor banks, crankcase heaters, space heaters.
- Stored electrical energy: VFD DC bus capacitors (wait manufacturer time; verify with meter), power factor correction capacitors, start/run capacitors (single-phase equipment), surge suppressors.
- Stored mechanical/fluid energy: pressurized lines (compressors), spring-loaded dampers, elevated loads, rotating inertia (fans), backspin on pumps, hot surfaces, refrigerant pressure.
- Try-start verification: after LOTO, attempt a start command to confirm isolation (where procedure allows).
- Prove your meter: live-dead-live method on a known source before and after absence-of-voltage testing.
2) Electrical checks in order (energized only when necessary)
When energized checks are required, use appropriate PPE, barriers, and one-hand technique where applicable. Keep the sequence: supply first, then control, then switching devices, then overload, then current/phase quality.
2.1 Line voltage (incoming power quality at the starter)
- Where to measure: at the line side of the disconnect/starter (L1-L2-L3 for three-phase; L-N or L-L for single-phase as applicable) and at the load side when commanded on.
- What you’re looking for: missing phase, undervoltage, excessive voltage drop under load, loose connection heating.
- Practical step: measure no-load (contactor open) and attempted run (contactor closed). A voltage that collapses only when starting points to supply impedance, loose terminations, or a locked rotor/mechanical jam drawing high current.
2.2 Control voltage (is the starter being told to run?)
- Measure at the coil: verify rated control voltage is present when the device should pull in.
- Trace the safety chain: if coil voltage is missing, work backward through series safeties (pressure switch, float, freezestat, overload auxiliary, E-stop). Identify the open device rather than bypassing blindly.
- Common field clue: intermittent operation often correlates with a marginal safety switch, loose control neutral, or vibration-sensitive terminal.
2.3 Contactor status (mechanical and electrical)
- Observe pull-in: does it pull in solidly or chatter? Chatter can indicate low control voltage, weak coil, or a control transformer issue.
- Check output: with contactor pulled in, verify voltage on the load side. If coil is energized but load-side voltage is missing or low on one pole, suspect burned/welded contacts or a failed pole.
- Heat evidence: discoloration at one pole often aligns with single-phasing and overload trips.
2.4 Overload state (tripped, mis-set, or nuisance trip)
- Confirm trip indication: many overloads show a mechanical flag or auxiliary contact state. Record whether it is manual or auto reset.
- Don’t just reset: if it tripped, assume overcurrent, phase loss, or overheating occurred. Reset only after checking for mechanical binding and verifying supply health.
- Quick discrimination: overload trips after seconds to minutes often indicate overload/locked rotor/phase loss; instantaneous trips point more toward short-circuit protection or severe fault.
2.5 Current draw vs FLA (compare, don’t guess)
Measure current on each line conductor with a clamp meter while the motor is running (or during a controlled start attempt if safe and permitted). Compare to the motor’s FLA and to typical load behavior.
- Normal load: current typically below or near FLA depending on load and service conditions.
- High current on all phases: mechanical overload (blocked fan, closed valve with certain pump types, high head pressure on compressor), undervoltage, wrong motor connection, or incorrect application.
- High current on one phase: phase imbalance, loose termination, failing contactor pole, or winding issue.
- Low current but poor performance: wrong rotation (three-phase), slipping belt, broken coupling, impeller damage, or airflow restriction causing fan to unload (fan laws can reduce current when airflow is blocked in some configurations).
2.6 Phase balance (voltage and current)
- Voltage balance: measure L1-L2, L2-L3, L3-L1 with the motor running. Significant imbalance can cause overheating and nuisance trips.
- Current balance: compare the three phase currents. A current imbalance larger than expected often points to supply imbalance, single-phasing, or internal motor issues.
- Practical note: if voltage is balanced but current is not, suspect motor or load; if voltage is unbalanced, start upstream (utility, transformer, connections, contactor, fuses).
3) Insulation and winding checks (de-energized, isolated, documented)
These tests help determine whether the motor windings and leads are intact and safe to energize. They must be done with the motor isolated from the circuit to avoid damaging controls and to avoid misleading readings.
Continue in our app.
You can listen to the audiobook with the screen off, receive a free certificate for this course, and also have access to 5,000 other free online courses.
Or continue reading below...Download the app
3.1 Continuity checks (quick “open/closed” screening)
- What it tells you: whether a winding circuit is open (broken lead, open thermal protector, failed connection).
- How: with power off and motor leads disconnected, check continuity between winding terminals per the motor’s lead configuration.
- Do: label and photograph leads before removal; verify meter zero/lead resistance.
- Don’t: rely on continuity alone to declare a motor “good.” A shorted turn can still show continuity.
3.2 Resistance comparison (phase-to-phase symmetry)
- What it tells you: gross imbalance between windings (open/shorted winding, bad connection).
- How: measure resistance between phase pairs (U-V, V-W, W-U) on a three-phase motor; compare readings—values should be close to each other (allowing for meter resolution and temperature).
- Practical tip: use a low-ohms meter if available; standard DMMs can be inaccurate at very low resistances. Record motor temperature if known.
- Don’t: compare your reading to a generic “ohms chart.” Compare phases to each other and to previous baseline readings if available.
3.3 Insulation resistance (IR) to ground (megohmmeter)
- What it tells you: condition of insulation between windings and ground (moisture, contamination, insulation breakdown).
- How: disconnect motor leads from starter/VFD/controls; test each winding lead to motor frame/ground using an appropriate test voltage per site practice and equipment rating.
- Do: discharge the windings after the test (many megohmmeters do this; verify), and keep others clear during testing.
- Don’t: megger through a VFD, soft starter, contactor electronics, or connected control wiring. Isolate the motor first to avoid equipment damage and false readings.
- Interpretation note: trending is powerful—compare to prior readings on the same motor. A sudden drop from historical values is often more meaningful than a single absolute number.
3.4 Ground fault and lead condition checks
- Inspect leads: especially in HVAC rooftops and wet areas—look for cracked insulation, oil-soaked cable, and rubbed-through sections at conduit entries.
- Check the junction box: loose wirenuts/lugs and moisture can mimic winding failure.
4) Mechanical checks (separate motor from load when needed)
Electrical symptoms often originate from mechanical problems. When current is high or the motor trips on overload, confirm the load can turn freely and is not forcing the motor into an overload condition.
4.1 Free rotation and bearing feel
- With power locked out: attempt to rotate the shaft/fan wheel by hand (as design allows). It should turn smoothly without grinding, tight spots, or scraping.
- Listen/feel: roughness suggests bearing damage; rubbing suggests misalignment, shifted fan wheel, or debris.
- Check endplay: excessive axial movement can indicate bearing or coupling issues.
4.2 Belt drives (fans and some pumps)
- Belt tension: too tight overloads bearings; too loose slips and reduces airflow/flow while current may drop.
- Sheave alignment: misalignment causes vibration and premature belt wear; can also create intermittent overload trips.
- Guarding: reinstall guards before any test run.
4.3 Couplings and alignment (pumps, compressors)
- Coupling condition: cracked elastomer inserts, loose set screws, worn keys can cause vibration and poor performance.
- Alignment: misalignment increases current and bearing temperature. If alignment is suspect, coordinate with mechanical maintenance for proper alignment tools and procedure.
4.4 Pump-specific checks
- Impeller blockage: debris in the volute/impeller can lock the shaft or overload the motor.
- Valve positions and strainers: closed discharge or suction restrictions can change load dramatically depending on pump type and system curve.
- Cavitation clues: rattling/gravel sound, fluctuating current/pressure; often a system issue (suction blockage, low NPSH conditions).
4.5 Fan and HVAC airflow checks
- Filters/coils/dampers: restrictions can change fan loading; verify dampers move freely and aren’t stuck.
- Fan wheel condition: buildup on blades can unbalance and increase load; broken blades reduce performance and can cause vibration trips.
4.6 Compressor and refrigeration-driven motor loads (high risk)
- Do not force repeated starts: repeated short-cycling can overheat motors and stress contactors.
- Check permissives: pressure switches, oil safety, crankcase heater status, and time delays can prevent starts by design.
- Mechanical lock: a locked compressor can present as high current/rapid trip; confirm with manufacturer procedure and coordinate with HVAC/refrigeration techs where required.
5) Decision points: repair vs replace, and what to document
5.1 Repair vs replace (practical criteria)
| Finding | Typical action | Notes |
|---|---|---|
| Loose/burnt termination, heat damage localized to lug | Repair connection, replace damaged lug/contactor pole if needed | Re-torque to spec; recheck current balance after repair |
| Contactor coil not energizing due to open safety device | Correct root cause (switch, wiring, process condition) | Document which device opened and why (pressure, temp, level) |
| Overload trips with high current and mechanical binding found | Fix mechanical issue first | Reset and verify running current is within expected range |
| IR (megger) low or trending downward significantly | Investigate moisture/contamination; consider drying/cleaning or replacement | Do not re-energize if insulation is unsafe per site standards |
| Winding resistance imbalance or open winding | Motor repair/rewind or replace | Also inspect leads and junction box for a simpler open |
| Repeated nuisance trips with balanced voltage but unbalanced current | Suspect motor internal issue or contactor pole | Confirm by swapping phases at starter (if permitted) to see if imbalance follows motor |
| Motor runs but performance low (airflow/flow) | Check belts, rotation, impeller/wheel, dampers/valves | Electrical readings may look “normal” while mechanical output is not |
5.2 What to document (minimum useful record)
- Complaint and conditions: who reported it, when it occurs, ambient/process conditions, any recent changes.
- Safety actions: LOTO points used, absence-of-voltage verification method, stored energy discharge steps.
- Electrical measurements: line voltages (all phase pairs), control voltage at coil, contactor status, overload state, running currents (each phase), any abnormal sounds/chatter.
- Insulation/winding results: continuity notes, phase-to-phase resistance readings, insulation resistance readings (test voltage used, temperature if known), and whether motor was isolated from controls.
- Mechanical findings: free rotation result, belt condition/tension, coupling condition, evidence of blockage, damper/valve positions.
- Corrective action: parts replaced, terminations reworked, cleaning performed, alignment/belt adjustment, and post-repair verification readings.
- Decision rationale: why repair was chosen vs replacement (time, cost, safety, insulation condition, repeated failures).
5.3 A repeatable field checklist (printable format)
SAFE MOTOR TROUBLESHOOTING (Fans/Pumps/Compressors/HVAC) 1-page flow 1) Verify complaint + conditions 2) Review diagram + interlocks 3) Visual inspection (motor/load/panel) 4) LOTO + stored energy + live-dead-live 5) Line voltage at starter (no-load and commanded run) 6) Control voltage at coil (trace safeties if missing) 7) Contactor: pull-in + load-side voltage 8) Overload: tripped? setting? aux contact state? 9) Running current each phase vs FLA + compare phases 10) Voltage/current balance check 11) De-energize, isolate motor leads 12) Continuity + phase resistance comparison 13) Insulation resistance to ground (megger) + discharge 14) Mechanical: free rotation, belts/coupling, blockage, dampers/valves 15) Decide: repair/replace + document all readings