1) Key terms electricians use on the job (simple definitions)
- Magnetic field (B-field): The invisible “force field” around a magnet or current-carrying conductor. In motors, it is produced mainly by current in the stator windings.
- Electromagnet: A coil that becomes magnetic when current flows. Motor stator windings act as electromagnets.
- Induction: Creating voltage/current in a conductor because the magnetic field through it is changing (or because the conductor is moving through a magnetic field).
- Rotor: The rotating part of the motor. In an induction motor, rotor current is induced (not directly wired to the supply).
- Stator: The stationary part that contains the windings that create the motor’s magnetic field.
- Rotating magnetic field (RMF): A magnetic field that appears to rotate around the stator bore. In three-phase motors it is produced naturally by the phase-shifted currents; in single-phase motors it is created using a start/run winding and capacitor (conceptually: “fake second phase”).
- Torque: Twisting force produced by the motor (turning effort). Higher torque demand generally requires higher current.
- Slip: The difference between synchronous speed (RMF speed) and actual rotor speed in an induction motor. Slip is required to induce rotor current and produce torque.
- Synchronous speed (Ns): Speed of the rotating magnetic field, set by line frequency and pole count.
- Rotor speed (Nr): Actual mechanical speed of the rotor/shaft.
- Load: The mechanical work the motor must do (fan, pump, compressor, conveyor, etc.).
- Back EMF: A voltage produced by the motor action that opposes the applied voltage. As load increases and speed drops, back EMF effectively reduces, allowing more current to flow.
- Locked-rotor current (LRA): High inrush current when the rotor is not turning (startup or stall). It is much higher than running current.
2) Annotated diagrams: stator/rotor interaction (what creates torque)
2.1 Three-phase induction motor: rotating field “drags” the rotor
Cross-section view (simplified) — looking into the motor end bell: ┌──────────────────────── Stator iron ────────────────────────┐ │ A-phase coil B-phase coil C-phase coil │ │ ( ) ( ) ( ) │ │ │ │ → Rotating Magnetic Field (RMF) at synchronous speed │ │ (field sweeps around the bore) │ │ │ │ ┌──────── Rotor (squirrel cage) ────────┐ │ │ │ || || || || || || || || │ │ │ │ bars + end rings (shorted conductors)│ │ │ └───────────────────────────────────────┘ │ └───────────────────────────────────────────────────────────────┘Annotations: 1) Stator currents create a rotating magnetic field (RMF). 2) RMF cutting rotor bars induces rotor voltage → rotor current flows (bars are shorted). 3) Rotor current creates its own magnetic field. 4) Interaction of stator RMF and rotor field produces torque in the direction of RMF rotation. 5) Rotor must run slightly slower than RMF (slip) so the RMF continues “cutting” rotor conductors.2.2 Why slip is not a “problem” but a requirement
Speed relationship (induction motor): RMF speed = Ns Rotor speed = Nr Slip speed = Ns - Nr Slip (%) = (Ns - Nr) / Ns × 100If Nr = Ns (zero slip): - RMF no longer cuts rotor bars (relative motion is ~0) - Induced rotor voltage drops toward 0 - Rotor current drops → torque drops toward 0So: some slip is necessary to keep inducing rotor current and producing torque.2.3 Load increase → more torque needed → more current drawn (cause-and-effect chain)
Mechanical load increases (fan damper opens, pump head increases, compressor loads) ↓Motor slows slightly (Nr decreases) ↓Slip increases (Ns - Nr increases) ↓Induced rotor voltage/current increases ↓Rotor magnetic field strengthens ↓Torque increases to match the load ↓Stator current increases (to supply the extra rotor power + losses) ↓More I²R heating in windings → higher temperature risk if overload persists2.4 Single-phase motors (job-relevant concept without deep design detail)
A single-phase supply does not naturally create a smoothly rotating field. To start and run, common single-phase induction motors use an auxiliary (start/run) winding and often a capacitor to create a phase shift. The result is an approximate rotating field that can produce starting torque and then running torque. The same practical rules still apply: more load → more slip → more current → more heat.
3) Short calculations: RPM vs pole count and frequency
3.1 Synchronous speed formula (RMF speed)
The rotating magnetic field speed is set by line frequency and the number of poles:
Ns (RPM) = 120 × f (Hz) / P (poles)
3.2 Quick examples (common field values)
| Frequency | Poles (P) | Ns (RPM) | Typical full-load Nr (RPM) | Typical slip (%) |
|---|---|---|---|---|
| 60 Hz | 2 | 3600 | 3450–3550 | ~1–4% |
| 60 Hz | 4 | 1800 | 1725–1775 | ~1–4% |
| 60 Hz | 6 | 1200 | 1140–1180 | ~2–5% |
| 50 Hz | 2 | 3000 | 2850–2950 | ~2–5% |
| 50 Hz | 4 | 1500 | 1420–1470 | ~2–5% |
| 50 Hz | 6 | 1000 | 940–980 | ~2–6% |
3.3 Step-by-step: calculate expected running RPM from nameplate slip
Scenario: A 60 Hz, 4-pole induction motor nameplate shows full-load speed 1740 RPM. Verify slip.
- Step 1: Compute synchronous speed:
Ns = 120 × 60 / 4 = 1800 RPM - Step 2: Compute slip RPM:
Ns − Nr = 1800 − 1740 = 60 RPM - Step 3: Compute slip percent:
Slip% = 60 / 1800 × 100 = 3.33%
3.4 Step-by-step: what happens to speed if frequency changes (VFD intuition)
Scenario: A 4-pole motor on a drive is run at 45 Hz instead of 60 Hz (ignoring slip change for a quick estimate).
Continue in our app.
You can listen to the audiobook with the screen off, receive a free certificate for this course, and also have access to 5,000 other free online courses.
Or continue reading below...Download the app
- Step 1:
Ns@60 = 120 × 60 / 4 = 1800 RPM - Step 2:
Ns@45 = 120 × 45 / 4 = 1350 RPM - Step 3: Expect rotor speed to be slightly less than 1350 RPM under load due to slip.
4) Practical takeaways for fans, pumps, and compressors (load characteristics → current and overheating)
4.1 The key field rule: current follows torque demand
For induction motors in normal service, when the mechanical load demands more torque, the motor increases slip to develop that torque, and stator current rises. This is why a motor that is “working harder” typically draws more amps and runs hotter.
4.2 Fans and centrifugal pumps: “variable torque” loads
Most HVAC fans and centrifugal pumps are variable-torque loads: torque demand rises rapidly with speed. A useful rule of thumb is the affinity behavior (for similar conditions):
- Flow is roughly proportional to speed.
- Pressure/head is roughly proportional to speed squared.
- Power is roughly proportional to speed cubed.
What this means on the job:
- If you reduce speed, current usually drops significantly (often a lot more than expected).
- If airflow is restricted (dirty filter, closed damper), the fan may draw less current because it is doing less work (depends on fan type and operating point).
- For pumps, a throttled discharge valve often reduces flow and can reduce power/current (again depending on where you are on the curve).
Step-by-step check when a fan/pump motor is overheating:
- Step 1: Measure line voltage and compare to nameplate. Low voltage can increase current for a given load and worsen heating.
- Step 2: Measure running current on all phases (three-phase) and compare to FLA. Look for imbalance; current imbalance often indicates voltage imbalance or winding issues.
- Step 3: Confirm mechanical condition: bearings, belt tension/alignment, rubbing, clogged pump strainers, partially seized impeller.
- Step 4: Compare operating point to expected: is the pump running far right on its curve (too much flow) or is the fan moving more air than designed (missing restrictions, wrong sheave)? Too much flow can overload the motor.
4.3 Positive displacement pumps and compressors: “constant torque” tendencies and high starting stress
Many compressors and positive displacement pumps behave closer to constant-torque loads over a wide speed range. They can demand substantial torque even at low speed, and they can be unforgiving during starting.
What this means on the job:
- Starting current is high (LRA), and starting time matters. Long acceleration time overheats windings quickly.
- Any added mechanical resistance (tight bearings, high head pressure, liquid slugging, blocked discharge) increases required torque and therefore current.
- If a compressor has trouble unloading, the motor may draw near-LRA longer than normal, causing rapid heating and nuisance trips.
Step-by-step check when a compressor motor draws high amps:
- Step 1: Verify supply voltage under load (watch for sag during start). Low voltage increases current and reduces starting torque.
- Step 2: Check for single-phasing or phase imbalance (three-phase). A missing phase can cause the motor to stall or overheat quickly.
- Step 3: Confirm the compressor is unloading properly (where applicable) and that discharge pressure/head is not abnormally high.
- Step 4: Measure running amps vs nameplate FLA after stabilization. If amps remain high, suspect mechanical overload, incorrect motor selection, or internal compressor issues.
4.4 Why “more load = more current” is usually true (and when it confuses people)
Electricians often expect any restriction to increase current, but with fans and centrifugal pumps, restriction can reduce the work being done. The motor current reflects mechanical power demand, not “how hard it looks like it’s trying.”
- Overloaded fan/pump case: Too much flow (operating far right on curve) → higher power demand → higher current → overheating.
- Restricted fan case (common): Dirty filter/closed damper → reduced airflow → often reduced power demand → lower current (even though the space is not getting air).
- Compressor case: Higher pressure differential or poor unloading → higher torque demand → higher current and heat.
4.5 Quick field cues tied to the concepts (slip, torque, current)
- Motor running slower than normal: often indicates increased slip due to overload, low voltage, or internal motor issues. Increased slip usually means increased current and heating.
- High current with normal mechanical load: check voltage imbalance, incorrect connections, failing bearings, or rotor issues (induction motors can draw extra current when torque production is inefficient).
- High current on one phase (three-phase): suspect voltage imbalance, loose termination, contactor issues, or developing winding fault.
- Frequent thermal trips: treat as an overheating symptom—verify actual current vs FLA, ambient temperature, cooling airflow over the motor, and duty cycle (starts per hour).