Free Ebook cover Electric Motor Basics for Electricians: Single-Phase and Three-Phase Essentials

Electric Motor Basics for Electricians: Single-Phase and Three-Phase Essentials

New course

12 pages

Capacitors, Relays, and Starting Switches: Field Diagnostics for Single-Phase HVAC Motors

Capítulo 8

Estimated reading time: 10 minutes

+ Exercise

1) Capacitor types (start/run) and safe discharge procedures

What the capacitors do in single-phase HVAC motors

Many single-phase HVAC motors use an auxiliary (start) winding to create a phase shift so the motor can develop starting torque. A capacitor in series with the auxiliary winding increases the phase shift and current to improve starting and/or running performance. When the capacitor circuit fails, the motor may hum, start slowly, trip on overload, or require a spin to start.

Start capacitor vs run capacitor (field-identification)

  • Start capacitor: High capacitance (typically tens to hundreds of µF), intermittent duty (seconds), usually in a plastic case, often used with a start relay/PTC or centrifugal switch. Provides high starting torque.
  • Run capacitor: Lower capacitance (typically a few to several tens of µF), continuous duty, usually metal can (oval/round), improves running efficiency, torque, and power factor; common in PSC (permanent split capacitor) blower and condenser fan motors.
  • Dual run capacitor: One can with three terminals (commonly labeled C, FAN, HERM on many HVAC units). Electrically it is two run capacitors sharing a common terminal.

Safety: discharge and verify

Capacitors can retain charge after power is removed. Treat every capacitor as energized until proven otherwise.

Step-by-step: safe discharge procedure (HVAC field method)

  1. De-energize and lock out the equipment. Verify with a meter at the contactor/load side as appropriate.
  2. Photograph and label wires before removal (especially dual run capacitors).
  3. Confirm the capacitor is isolated: remove at least one lead from the capacitor terminal(s) so you are not discharging through other components.
  4. Discharge using a resistor (preferred): place a 2 kΩ to 20 kΩ, 2 W (or higher) resistor across the capacitor terminals for several seconds (larger µF may need longer). This limits current and reduces terminal damage.
  5. Verify zero volts: measure DC volts across the capacitor terminals; confirm near 0 V.
  6. Do not “dead short” as a routine practice: shorting with a screwdriver can pit terminals, damage internal connections, and create arc flash risk. Use a resistor method whenever possible.

2) How to test capacitors (capacitance reading, visual inspection, interpreting tolerance)

Visual inspection: what matters and what doesn’t

  • Bulging top (metal can) or swollen case: strong indicator of failure.
  • Oil leakage (some run caps): replace.
  • Burn marks, melted terminals, loose spade lugs: can cause intermittent starting; repair/replace terminals and consider capacitor replacement.
  • Rusty can: not automatically failed, but check terminals and mounting; moisture can lead to corrosion-related connection issues.

Capacitance test with a meter (best practice)

Use a DMM with capacitance function or a dedicated capacitor tester. Test with the capacitor discharged and at least one lead removed from circuit.

Step-by-step: measuring capacitance

  1. Confirm the capacitor is discharged and isolated (one lead removed minimum).
  2. Set meter to capacitance (often marked CAP or µF).
  3. Connect leads: for a two-terminal capacitor, measure across the two terminals. For a dual run capacitor, measure C to FAN (fan section) and C to HERM (compressor section).
  4. Wait for the reading to stabilize; record the value.
  5. Compare to the nameplate µF rating and tolerance printed on the capacitor.

Interpreting tolerance (pass/fail)

Most HVAC run capacitors are marked with a tolerance such as ±5% or ±6%; some are ±10%. Start capacitors may have wider tolerances (often printed on the case).

Example ratingToleranceAcceptable range
10 µF±6%9.4 to 10.6 µF
45 µF±5%42.75 to 47.25 µF
5 µF±10%4.5 to 5.5 µF

Field rule: if the measured value is outside the printed tolerance, replace. If it is within tolerance but symptoms persist, continue diagnosing the start device, wiring, and mechanical load.

Continue in our app.

You can listen to the audiobook with the screen off, receive a free certificate for this course, and also have access to 5,000 other free online courses.

Or continue reading below...
Download App

Download the app

When capacitance reading can mislead

  • Intermittent internal connection: may read OK on the bench but fail under vibration/heat. Look for loose terminals, heat discoloration, or a history of intermittent starts.
  • Wrong test setup: measuring in-circuit can backfeed through windings and give false readings.
  • Temperature effects: capacitance can drift with temperature; borderline readings in extreme heat may justify replacement in critical HVAC service.

3) Diagnosing start relays/PTC devices and centrifugal switches

Start relays and PTC devices: what they control

In capacitor-start designs, the start capacitor must be removed from the circuit after the motor accelerates. This is done by a start relay (potential relay or current relay) or a PTC (positive temperature coefficient) device. If the start capacitor stays in too long, it can overheat and fail; if it never engages, the motor may hum and not start.

Potential relay (common on compressor start kits)

  • Concept: the relay coil senses rising back EMF (voltage) as the motor speeds up; at a set voltage it opens contacts to drop out the start capacitor.
  • Common failures: welded contacts (start cap stays in), open coil (start cap never engages), wrong relay rating, loose spade terminals.

Current relay (less common in modern HVAC but encountered)

  • Concept: high inrush current energizes the relay coil to close contacts and apply the start capacitor; as current drops with speed, contacts open.
  • Common failures: contacts stuck open (no start assist), contacts stuck closed (start cap stays in), coil issues.

PTC start device

  • Concept: cold PTC has low resistance allowing start circuit current; it heats quickly and resistance rises, effectively removing the start circuit.
  • Common failures: cracked disc, permanently high resistance (no start), poor thermal contact, intermittent behavior when cycling quickly (short off-time).

Field checks for relays/PTC (practical)

  1. Visual/connection check: verify correct wiring, tight terminals, no heat damage.
  2. Contact check (relay): with power off, check continuity of relay contacts in the expected “rest” state per wiring diagram. If contacts are welded or open when they should be closed, replace.
  3. Coil check (relay): measure coil resistance; an open coil indicates failure. Compare to known-good or manufacturer data when available.
  4. PTC resistance check: when cool (power off long enough), measure resistance; extremely high resistance cold often indicates a failed PTC. If it reads reasonable cold but fails hot, suspect thermal aging or short cycling issues.

Centrifugal switch (common in some single-phase motors)

A centrifugal switch is a mechanical speed-operated switch inside the motor that disconnects the start winding and start capacitor once the rotor reaches a set speed. It is common in certain capacitor-start induction-run (CSIR) motors and other designs used in some HVAC and general-purpose applications.

Typical centrifugal switch failure modes

  • Stuck open: start circuit never engages → hum/no start or starts only when spun.
  • Stuck closed: start circuit stays engaged → high current, overheating, possible capacitor failure, noisy operation.
  • Dirty/pitted contacts: intermittent starting, especially after long off periods or in dusty environments.
  • Mechanical binding: broken springs/weights or rubbing due to wear.

Step-by-step: diagnosing a centrifugal switch (field approach)

  1. Confirm symptoms suggest start circuit issues (see flowcharts below).
  2. De-energize, lock out, and verify zero energy.
  3. Access the switch if the motor design allows (end bell removal). Note: many HVAC motors are not intended for field disassembly; follow manufacturer guidance.
  4. Inspect for dust/oil contamination, burned contacts, broken springs, or stuck mechanism.
  5. Check continuity across switch contacts at rest (motor stopped). It should match the design (commonly closed at rest for start circuit engagement).
  6. Manually actuate the mechanism (gently) and verify contacts open/close reliably.
  7. Corrective action: light cleaning may restore function, but if contacts are badly pitted or mechanism is worn, replacement of the switch assembly or motor is often the reliable repair.

4) Symptom-based flowcharts

Flowchart A: Motor hums then trips (overload opens)

Symptom: Hums, little/no rotation, then trips on overload or breaker (after seconds to minutes)  
  |  
  +-- Step 1: Verify correct supply voltage at motor terminals under attempt-to-start load  
  |       - Low voltage can mimic capacitor failure  
  |  
  +-- Step 2: Check for mechanical binding (fan blade, seized bearings, tight belt)  
  |       - If shaft hard to turn (power off), fix mechanical issue first  
  |  
  +-- Step 3: Test run capacitor (PSC) or start/run capacitors (CSIR/CSR)  
  |       - If out of tolerance or visually damaged: replace  
  |  
  +-- Step 4: If start capacitor system present, test start relay/PTC or centrifugal switch  
  |       - Start device not engaging = hum/no start  
  |       - Start device stuck in = high current/overheat  
  |  
  +-- Step 5: If capacitors and start device test OK, evaluate motor windings/insulation  
          - At this point suspect motor internal fault or incorrect wiring

Flowchart B: Starts only when spun (hand-start)

Symptom: Motor will start if spun by hand (or with a push), otherwise hums  
  |  
  +-- Step 1: Confirm it is a design that should self-start  
  |       - Most HVAC fan motors should self-start  
  |  
  +-- Step 2: Test run capacitor (PSC motors)  
  |       - Most common cause: weak/open run capacitor  
  |  
  +-- Step 3: Check auxiliary winding circuit connections  
  |       - Loose spade, burnt terminal, wrong wiring after service  
  |  
  +-- Step 4: If start capacitor system present, verify start device closes at standstill  
          - Centrifugal switch stuck open or relay/PTC not engaging

Flowchart C: Intermittent starting (works sometimes, fails other times)

Symptom: Sometimes starts normally; other times hums, starts slow, or trips  
  |  
  +-- Step 1: Inspect terminals and crimps on capacitor and relay/PTC  
  |       - Heat-discolored or loose spades cause intermittent start circuit loss  
  |  
  +-- Step 2: Check capacitor mounting and vibration  
  |       - Loose strap can fatigue terminals; replace connectors as needed  
  |  
  +-- Step 3: Measure capacitance cold and after heat soak (if possible)  
  |       - Borderline capacitors may fail hot  
  |  
  +-- Step 4: For PTC devices, consider short-cycling behavior  
  |       - If restarted too soon, PTC may still be hot (high resistance)  
  |  
  +-- Step 5: For centrifugal switch, inspect for dust/oil and contact pitting  
          - Intermittent contact = intermittent start winding engagement

5) Replacement criteria (µF rating, voltage rating, temperature and mounting)

Capacitor selection rules that prevent repeat failures

  • µF rating: match the motor or equipment specification. Do not “upsize” capacitance to force a start; incorrect µF can overheat the auxiliary winding, reduce efficiency, or cause nuisance trips. For dual run capacitors, both sections must match (e.g., 45/5 µF).
  • Voltage rating: replacement must be equal or higher than the original (e.g., replace 370 VAC with 440 VAC is acceptable; replace 440 VAC with 370 VAC is not). Higher voltage rating generally improves robustness in HVAC environments.
  • Duty type: use a run capacitor for continuous duty and a start capacitor only for intermittent start duty. They are not interchangeable.
  • Temperature rating: choose a capacitor rated for the ambient conditions (common HVAC run caps are 70°C or higher). High-heat condenser compartments benefit from higher temperature ratings.
  • Mounting and case style: match physical size and mounting strap/bracket (round vs oval). Ensure terminals are protected from vibration and moisture; use proper insulated terminals where required.
  • Terminal quality: replace overheated spade connectors; a new capacitor on a loose/burnt connector can fail prematurely due to arcing and heat.

Step-by-step: replacing a dual run capacitor correctly

  1. Confirm power is off and capacitor is discharged.
  2. Record the existing rating (example: 45/5 µF 440 VAC) and take a clear photo of wiring.
  3. Label wires by terminal group (C, FAN, HERM) before removal.
  4. Install the replacement with the same µF ratings and equal/higher voltage rating.
  5. Move wires one terminal group at a time to avoid cross-connection.
  6. Secure the capacitor firmly; ensure no terminals can short to chassis and that the cover fits without pinching wires.
  7. Run the equipment and verify normal start, normal sound, and stable operation; if symptoms persist, return to start device and mechanical checks.

When to replace the start relay/PTC or centrifugal switch vs the whole motor

  • Replace the relay/PTC when capacitor values are correct but the start capacitor is not being applied or is staying applied (evidence of repeated start capacitor failures, relay contact issues, or PTC behavior consistent with failure).
  • Replace/repair the centrifugal switch if accessible and clearly faulty (stuck, pitted, broken mechanism). If the motor is sealed or disassembly is not recommended, motor replacement may be the practical option.
  • Consider motor replacement if repeated capacitor/start device replacements do not resolve symptoms, or if there is evidence of winding damage (burn odor, discoloration, persistent high current, or insulation test failures performed per your shop practice).

Now answer the exercise about the content:

When replacing an HVAC motor capacitor, which selection rule best helps prevent repeat failures and motor damage?

You are right! Congratulations, now go to the next page

You missed! Try again.

Correct replacements keep the same µF value and use an equal or higher voltage rating. Upsizing capacitance or swapping start/run types can overheat windings, reduce efficiency, or cause repeated failures.

Next chapter

VFD and Soft Starter Fundamentals for Electricians: What Changes in Wiring, Protection, and Testing

Arrow Right Icon
Download the app to earn free Certification and listen to the courses in the background, even with the screen off.