Single-Pole Switching for Lighting: Reliable On/Off Control

Capítulo 2

Estimated reading time: 10 minutes

+ Exercise

What a Single-Pole Switch Does (One Load, One Location)

A single-pole switch provides simple on/off control of one lighting load (one fixture or a group of fixtures that turn on together) from one location. Electrically, it is just a controlled break in the hot (line) conductor: when the switch is ON, the hot is connected through to the load; when OFF, the hot is opened and the light turns off.

Key idea: a standard single-pole switch does not “create” power or “use” neutral. It typically switches only the hot. Neutral is normally spliced through in the box (or at the fixture) so the load has a complete circuit when the switch is ON.

Symbol Recognition and Terminal Identification

Common symbols you’ll see

  • Single-pole switch symbol: a simple break with a pivoting contact in the hot conductor.
  • Ground symbol: three descending horizontal lines (earth/ground).

Switch terminals (what to look for on the device)

  • Two brass-colored screws: these are the switch’s current-carrying terminals. On many single-pole switches they are interchangeable (either can be line or load). Some devices label one as COM (common) or LINE; follow the label if present.
  • Green screw: equipment grounding conductor (EGC) connection.
  • Back-wire clamp holes (on some “spec-grade” switches): accept a straight conductor under a clamp tightened by the side screw.
  • Backstab holes (on some residential switches): push-in spring contacts. These are a common failure point and are best avoided for reliability.

Common vs. ground (and what “common” means here)

On a single-pole switch, “common” (if marked) refers to the terminal that the manufacturer intends for the incoming hot (line). Ground is always the green screw and bonds the metal yoke and faceplate (if metal) to the equipment grounding system.

Standard Wiring Patterns (Power to Switch vs. Power to Fixture)

Single-pole lighting is usually wired in one of two common patterns. The difference is where the always-hot feed enters first.

Pattern A: Power enters the switch box (power-to-switch)

This is the most straightforward for troubleshooting because the switch box contains the always-hot feed, the switched-hot out to the light, and usually the neutrals spliced together.

Continue in our app.

You can listen to the audiobook with the screen off, receive a free certificate for this course, and also have access to 5,000 other free online courses.

Or continue reading below...
Download App

Download the app

Panel feed (2-wire + ground)      Cable to light (2-wire + ground)  Fixture
Black (hot) -------------------. Hot (switched)
|
[ Single-pole ]
|
Black (to light) --------------'---------------------------------> Fixture hot

White (neutral) -----------------------------------------------> Fixture neutral
Grounds all tied + to switch green screw + to box (if metal)

What’s in the switch box: line hot (black), load hot (black to fixture), neutrals (whites) tied together, grounds tied together and to the switch.

Pattern B: Power enters the fixture box first (power-to-fixture)

In this pattern, the feed enters the fixture box, and a cable (often called a “switch loop”) runs down to the switch. The switch still must interrupt the hot. Depending on cable type and local code practices, the switch box may or may not have a neutral present. In modern work, a neutral is often required in switch boxes for smart controls; if your cable provides it, you’ll splice it through.

Panel feed enters fixture box first

Fixture box: Switch box:
Feed hot (black) -----. .---- to switch terminal (LINE/COM)
| |
'---> to switch (hot down) [ Single-pole ] ---> switched hot back up

Switched hot back up ------------------------------> Fixture hot
Feed neutral (white) ------------------------------> Fixture neutral
Grounds tied throughout + switch green screw

Important: In a switch-loop arrangement, the conductor colors must be used correctly. If a white conductor is repurposed as hot, it must be re-identified (typically with black or red marking) where accessible. Never assume white is neutral without verifying the wiring method.

Proper Splicing Technique and Pigtailing (Reliability in the Box)

Why pigtails matter

Pigtailing means using a short piece of wire to connect multiple conductors to a single device terminal. This improves reliability and serviceability: removing the switch later doesn’t break continuity to other conductors that must remain connected.

Typical pigtails in a single-pole switch box

  • Ground pigtail: grounds tied together with a pigtail to the switch green screw (and to the metal box if present).
  • Hot feed pigtail (when the feed must continue onward): if the always-hot feed also supplies other circuits/cables in the box, splice the feed hot to the onward hot(s) and add a pigtail to the switch LINE/COM.
  • Neutral splice: neutrals are typically spliced together and do not land on a standard mechanical switch.

Splicing steps (wirenut-style) for a solid connection

  1. Match conductor type and size: use the correct connector for the gauge (e.g., 14 AWG vs 12 AWG) and for solid vs stranded if applicable.
  2. Strip to the correct length: follow the connector and device strip gauge. Too short reduces contact; too long risks exposed copper.
  3. Pre-twist when appropriate: many electricians pre-twist solid conductors for strength before installing the connector (follow connector instructions).
  4. Install the connector firmly: tighten until conductors are secure and no bare copper is visible below the skirt.
  5. Perform a pull test: tug each conductor individually to confirm it is captured.
  6. Fold conductors neatly: place splices to the back of the box, keep the switch leads accessible, and avoid sharp bends that stress the copper.

Preferred device connection methods

  • Side-screw with a hooked conductor: wrap clockwise so tightening draws the loop in.
  • Back-wire clamp (screw-tightened): reliable and fast when used correctly.
  • Avoid backstabs: push-in spring contacts can loosen over time from heat cycling and vibration, causing flicker or failure.

Switch Rating Selection (Amps, Voltage, and Load Type)

Voltage rating

Most residential lighting circuits use switches rated 120 VAC (often also marked 277 VAC for commercial). Use a switch with a voltage rating at least equal to the circuit voltage.

Current (amp) rating

Common ratings are 15 A and 20 A. The switch must be rated for the circuit and load. A 15 A switch is typical on 15 A lighting circuits; for 20 A circuits, use a 20 A rated switch.

Lighting vs. motor-rated switches

  • Lighting loads: standard switches are generally fine for incandescent/halogen and many LED drivers within rating.
  • Motor loads (bath fans, disposals, some ventilators): use a switch specifically rated for motor duty (often marked HP rating). Motors have higher inrush current.

LED considerations for a simple on/off switch

Even without dimming, some LED drivers draw brief inrush current. Choose a quality switch (spec-grade or reputable brand) if the circuit controls many LED fixtures, and prioritize solid terminations (clamp/side-screw) to prevent nuisance flicker from high-resistance connections.

Step-by-Step Wiring Sequences (with Annotated Diagrams)

The sequences below focus on the wiring logic and reliable terminations. Wire colors shown are typical; always follow the actual cable/conductor identification in the box.

Sequence 1: Power-to-switch (feed in switch box)

Switch box conductors (typical):
Feed: Black (LINE hot), White (neutral), Bare/Green (ground)
To light: Black (LOAD hot), White (neutral), Bare/Green (ground)

Connections:
1) Neutrals: Feed white + Light white --wirenut--> (neutral splice)
2) Grounds: All grounds tied + pigtail to switch green screw
3) Hot: Feed black --> switch LINE/COM terminal
4) Switched: Light black --> switch other brass terminal
  1. Prepare conductors: strip insulation to device/connector gauge; straighten ends for clamp-backwire if used.
  2. Splice neutrals: connect feed neutral to fixture neutral (and any onward neutrals) with an approved connector; tuck to back.
  3. Splice grounds + pigtail: tie all grounds together; add a ground pigtail to the switch green screw (and bond metal box if present).
  4. Terminate the hot feed: connect the incoming hot (line) to the switch LINE/COM (or either brass screw if not marked).
  5. Terminate the switched hot: connect the conductor going to the fixture hot to the remaining brass screw.
  6. Dress the box: fold splices back, keep the switch conductors relaxed (no tension), align the device.

Sequence 2: Power-to-fixture (feed in fixture box, switch loop)

Fixture box conductors (typical):
Feed in: Black (hot), White (neutral), Ground
Cable to switch: two conductors + ground (colors vary by method)

Goal:
Feed hot goes DOWN to switch, then switched hot returns UP to fixture hot.
Neutral stays at fixture (and may or may not be present in switch box).
  1. At the fixture box: identify feed hot and feed neutral (incoming cable from panel).
  2. Create the switch loop hot down: splice feed hot to the conductor going down to the switch that will serve as line to switch (often black). If a white is used as hot in the loop, it must be re-identified as hot.
  3. Return switched hot up: connect the conductor returning from the switch (often red or black depending on cable) to the fixture hot lead.
  4. Neutral connection: connect feed neutral to the fixture neutral lead (and to any onward neutrals).
  5. Grounding: tie grounds together; bond the fixture strap/box as required; ensure the switch box ground is continuous and lands on the switch green screw.
  6. At the switch box: two switch terminals only: the down-going hot lands on one brass screw (LINE/COM if marked), and the return switched-hot lands on the other brass screw. Ground to green screw. Neutral (if present) is spliced through and does not land on the switch.

Troubleshooting Common Failures (and What They Look Like)

Loose backstabs

Symptoms: intermittent light, flicker when tapping the switch or wall, works for weeks then fails, warm switch. Fix: move conductors from backstab to side-screw or back-wire clamp; trim/strip fresh copper; torque firmly.

Poor wirenut connections

Symptoms: dead light, flicker, heat smell, melted connector, multiple lights affected if feed-through splice is failing. Fix: redo splice: correct connector size, proper strip length, firm twist, pull test, no exposed copper.

Open neutral

Symptoms: switch appears to have hot present but light won’t turn on; voltage readings can be misleading due to phantom voltage; other loads on the same neutral path may behave oddly. Where to look: neutral splice in switch box (Pattern A) or neutral connection at fixture (Pattern B). Fix: re-make neutral splice/termination at the point where neutral is distributed.

Switched neutral mistake (switching the white instead of the hot)

Symptoms: light turns on/off but the fixture socket may remain energized even when “off,” creating a shock hazard during lamp changes or servicing. Clue: hot is tied straight through to fixture, and neutral is routed through the switch. Fix: rewire so the switch interrupts the hot conductor; neutral should be continuous to the fixture.

Misidentified conductors in a switch loop

Symptoms: breaker trips, light always on, or switch does nothing. Fix: positively identify which conductor is feed hot down and which is switched hot up; re-identify any repurposed white as hot; correct terminations at both boxes.

Verification Checklist (Off-Power and On-Power)

Off-power checks (continuity and visual)

  • Visual: no damaged insulation, no nicked copper, no bare copper exposed outside terminals/connectors.
  • Terminal security: side screws tight; clamp-backwire screws tight; no conductors in backstabs (preferred).
  • Grounding: grounds tied; ground pigtail to switch green screw; metal box bonded if present.
  • Continuity (with power off): switch should read open when OFF and closed when ON between its two brass terminals (device removed or isolated as needed for accurate testing).
  • Neutral integrity: neutral splice is firm (pull test each white).

On-power functional checks

  • Switch operation: light turns fully on and fully off without flicker.
  • Heat check: after a few minutes ON, switch should not feel unusually warm (warmth can indicate a high-resistance connection).
  • Correct switching: verify the hot is being switched (fixture should not have energized hot at the lamp holder when switch is OFF, depending on fixture design and access).

Plate installation considerations

  • Device alignment: straighten the switch before tightening the yoke screws fully; avoid twisting that stresses conductors.
  • Do not overtighten the wall plate: overtightening can crack plates and can bind the switch toggle.
  • Box fill and conductor dressing: ensure conductors fold without sharp kinks; keep splices behind the device so the switch sits flush.

Now answer the exercise about the content:

In a standard single-pole lighting circuit, which conductor should the switch interrupt to provide safe on/off control?

You are right! Congratulations, now go to the next page

You missed! Try again.

A single-pole switch is a controlled break in the hot (line) conductor. Switching neutral can leave parts of the fixture energized when “off,” creating a shock hazard. Ground is never switched.

Next chapter