What “maintenance and readiness” really means
Backup power fails most often for ordinary reasons: old fuel, a weak starting battery, clogged air flow, neglected oil, or a control setting that drifted. “Maintenance” is the recurring service that keeps the machine healthy. “Readiness” is everything around the machine—labels, supplies, cords, and transfer equipment—so you can produce power quickly and predictably when the outage hits.
Maintenance schedule (portable generators)
Use your generator’s manual as the final authority for intervals and oil type. The schedule below is a practical baseline that works for most small gasoline/dual-fuel portables.
Every use (before starting)
- Oil level: Check dipstick on level ground; top off to the correct mark.
- Air intake and cooling: Clear debris from intake screen and cooling fins; confirm nothing is blocking airflow.
- Fuel and leaks: Look for fuel smell, wet spots, cracked fuel lines, loose clamps.
- Fasteners and mounts: Quick check for loose bolts, damaged feet, or cracked frame welds.
- Extension cords and plugs: Inspect for cuts, melted blades, loose ends; confirm cord rating matches expected load.
After first break-in (new engine)
- Oil change: Many engines require the first oil change at 5–10 hours. This removes initial wear-in debris.
Every 25–50 hours of run time (or at least annually)
- Oil change: Change oil more often in hot weather, dusty conditions, or heavy loads. Keep a log of run hours.
- Air filter inspection: Tap out foam/paper prefilter dust; replace if stained with oil, torn, or heavily loaded.
Every 100 hours (or annually, whichever comes first)
- Air filter service: Replace paper element; wash and re-oil foam element if applicable (follow manual).
- Spark plug inspection: Remove, inspect color and deposits, check gap, replace if worn or fouled.
- Spark arrestor (if equipped): Clean screen to prevent restriction.
Every 200–300 hours (or every 2–3 years for low-use units)
- Spark plug replacement: Replace proactively if the generator is critical for medical or sump loads.
- Fuel system refresh: Replace in-line fuel filter (if equipped) and inspect fuel shutoff valve operation.
Step-by-step: oil change (portable)
- Warm the engine briefly (2–3 minutes) so oil flows, then shut down and let it cool enough to handle safely.
- Shut off fuel (valve to OFF) to reduce spill risk.
- Place a drain pan under the drain plug or drain tube.
- Remove drain plug and open the fill cap/dipstick to vent; drain fully.
- Reinstall plug with correct torque (snug, not over-tight).
- Refill with specified oil to the correct level; recheck after a minute.
- Run 1–2 minutes, shut down, and recheck level and leaks.
- Log hours/date on a tag or in a notebook stored with the generator.
Step-by-step: spark plug check (portable)
- Remove plug boot and clean around the plug so debris doesn’t fall into the cylinder.
- Remove plug with the correct socket.
- Inspect: dry light-tan is typical; wet fuel smell suggests flooding; oily deposits suggest oil consumption; white blistering suggests overheating/lean condition.
- Check gap with a feeler gauge and adjust if the plug type allows.
- Reinstall by hand to avoid cross-threading, then tighten to spec; reinstall boot firmly.
Maintenance schedule (standby generators)
Standby units add two critical systems beyond the engine: an automatic starting battery/charger and electronic controls (controller, sensors, transfer logic). Many standby generators also have built-in exercise scheduling and fault logs—use them.
Monthly
- Visual inspection: Check enclosure vents, rodent nests, oil/coolant drips, loose conduit fittings.
- Controller status: Confirm no active alarms; review event/fault history.
- Battery health: Verify charger indicates normal; inspect terminals for corrosion.
- Exercise run: Confirm the scheduled exercise occurred (or run a manual exercise). Prefer an exercise that includes a brief load transfer if your setup and local rules allow it.
Quarterly (or every 6 months in mild climates)
- Air filter check: Replace if dirty or if the site is dusty/pollen-heavy.
- Oil level: Confirm level and condition; look for fuel dilution smell.
- Software/controls check: Confirm time/date, exercise schedule, and any utility monitoring settings are correct after power events. If the manufacturer provides firmware updates, apply them only per their guidance (often via authorized service).
Annually (or per manufacturer hours)
- Oil and filter change: Even low-hour standby engines benefit from annual oil changes due to moisture and acids.
- Spark plugs: Inspect/replace per spec.
- Battery test: Perform a load test or conductance test; replace proactively at the recommended age (often 3–5 years depending on battery type and climate).
- Cooling system (liquid-cooled units): Check coolant level and concentration; inspect hoses and clamps.
- Full functional test: Verify start, warm-up, transfer, stable voltage/frequency under load, and retransfer.
Battery tenders vs built-in chargers
Portable generators with electric start often sit for long periods. A small battery tender/maintainer (not a high-current charger) keeps the starting battery topped off without overcharging. Connect it when the generator is stored, and route the cord so it won’t be pinched or exposed to water.
Standby generators typically include an integrated battery charger. Your job is to verify it’s working (status indicators, voltage checks) and that terminals are clean and tight. If the controller logs “battery charger fault” or “low battery,” treat it as a readiness emergency.
Continue in our app.
You can listen to the audiobook with the screen off, receive a free certificate for this course, and also have access to 5,000 other free online courses.
Or continue reading below...Download the app
Fuel system care: keeping fuel from becoming the failure point
Gasoline: stabilizers and rotation
Gasoline degrades over time and can form varnish that clogs jets and sticks float needles. Use a stabilizer for any stored fuel and for fuel left in the generator tank during standby periods.
- Stabilize fresh fuel: Add stabilizer at the time you buy fuel (not months later). Mix thoroughly.
- Rotate stock: Use the oldest cans in vehicles or equipment and replace with fresh fuel on a schedule you can keep (monthly/quarterly depending on storage conditions).
- Container discipline: Use approved containers, keep caps tight, store away from heat, and label purchase date.
Carburetors: drain or run dry (portable)
Small engines often fail to start because the carburetor bowl contains old fuel. Two common approaches are (1) draining the bowl or (2) running the carburetor dry. Follow your manual; some carburetors have a drain screw, others do not.
Step-by-step: run the carburetor dry
- With the generator running and loads removed, turn the fuel valve to OFF.
- Let the engine continue until it stalls.
- Turn ignition switch to OFF.
- If equipped, open the carb bowl drain briefly to remove the last teaspoon of fuel.
Step-by-step: drain the carburetor bowl
- Shut down and allow the engine to cool.
- Close the fuel valve.
- Place a small container under the carb drain.
- Open the drain screw/bolt carefully; drain fully; close securely.
- Wipe spills and check for seepage.
Propane (LP): tank checks and regulator awareness
Propane stores well, but the system still needs inspection.
- Tank level: Don’t wait for winter storms to discover the tank is low. Set a refill threshold (for example, refill at 30–40%).
- Visual inspection: Look for damaged hoses, cracked protective boots, corrosion on fittings, or impact damage to the tank.
- Regulator vent: Keep the regulator vent pointed down and unobstructed; keep it free of mud/ice.
- Leak checks: After any cylinder swap or service, use a leak-detection solution on connections (bubbles indicate a leak). If you smell gas, stop and call a qualified technician.
Diesel (if applicable): water and microbial control
Diesel can suffer from water contamination and microbial growth in storage. If your home setup uses diesel, follow a strict storage plan: keep tanks full to reduce condensation, use biocide when recommended, and drain water separators if equipped.
Exercise runs and periodic load testing (verifying real-world performance)
“It starts” is not the same as “it carries the house loads.” Exercise runs keep seals lubricated and recharge batteries, but load testing is what proves the generator can deliver stable power under realistic demand.
Exercise run: what to do
- Portable: Run monthly for 15–30 minutes. During the run, plug in a moderate load (for example, a space heater or heat gun) to bring the engine up to operating temperature and reduce wet-stacking on larger units.
- Standby: Confirm the automatic exercise schedule is enabled and matches your preferences (day/time). If your unit supports it, schedule an exercise that includes a transfer occasionally to verify the full chain works.
Load test: a practical method
Plan a controlled test when you can tolerate an interruption. The goal is to confirm starting, voltage/frequency stability, and that priority circuits behave as expected.
- Prepare meters: Use a plug-in power meter or multimeter (if qualified) to observe voltage; some standby controllers display frequency/voltage.
- Start with a known load: Add loads in steps (e.g., 25%, 50%, 75% of expected outage load). Avoid guessing—use appliances with known wattage or a load bank if available.
- Watch for symptoms: Excessive engine hunting, flickering lights, breaker trips, or voltage sag indicates issues (fuel delivery, governor, overload, or wiring problems).
- Run long enough: 20–30 minutes at a meaningful load is more revealing than a 2-minute test.
- Record results: Date, ambient temperature, fuel type, loads applied, and any alarms.
| What you observe | Likely cause | What to do next |
|---|---|---|
| Starts, then dies after a minute | Carburetor varnish, fuel valve issue, clogged vent | Drain/run dry, clean carb, check tank vent and fuel filter |
| Runs but surges at no load | Governor/carb issue, air leak | Inspect air filter, fuel quality; service carb/governor |
| Voltage low under load | Overload, engine not reaching RPM, wiring/connection loss | Reduce load; verify RPM/frequency; inspect cords/inlet connections |
| Standby shows battery alarm | Weak battery, charger fault, corroded terminals | Test/replace battery; inspect charger output and connections |
Readiness checklist (what to keep ready, labeled, and nearby)
Readiness is about reducing decision-making during a stressful outage. Build a small “power outage kit” and keep it where you connect and operate.
Panel and circuit readiness
- Labeled circuits: Clearly label which circuits are intended for backup operation (and which are not). Use durable labels that won’t peel.
- Printed operating steps near the panel: Post a laminated one-page checklist at eye level near the transfer equipment/panel. Include: start steps, connection steps, load add sequence, and shutdown steps.
- Contact list: Include electrician/service company number and generator model/serial number.
Consumables and spares
- Spare oil: Keep at least one full oil change worth of the correct oil type/viscosity.
- Oil filter(s): For standby and filter-equipped portables, keep at least one spare filter.
- Air filter(s): Keep a spare if your environment is dusty or wildfire smoke is common.
- Spark plug(s): Keep one set plus the correct socket and gap tool.
- Funnel, drain pan, rags: Store together to avoid improvising during an outage.
Cords and connection gear
- Properly rated cords: Keep the correct gauge and connector type for your generator and expected load. Mark cords with length and amp rating.
- Spare cord seals/caps: If your inlet/cord uses weather caps or gaskets, keep spares to maintain weather resistance.
- Strain relief plan: Have a way to route cords so they won’t be pinched by doors or tripped over (hooks, cable ramps, or a dedicated pass-through).
Seasonal inspection of inlet/transfer equipment
At least twice per year (for example, spring and fall), inspect the parts that make connection reliable.
- Inlet box: Check for cracked cover, water intrusion, corrosion on prongs, and tight mounting.
- Cord ends: Look for discoloration, looseness, or heat damage; confirm blades are tight and clean.
- Transfer equipment exterior: Verify labeling is intact and the mechanism operates smoothly (do not open energized equipment).
- Fastener and conduit check: Confirm fittings are tight and there’s no movement that could stress wiring.
- Weather readiness: Ensure gaskets seal, covers close fully, and snow/ice won’t block access.
Simple tracking systems that prevent missed maintenance
Run-hour and service log
Keep a log attached to the generator handle (portable) or inside the standby enclosure (if allowed by the manufacturer). Record:
- Date and run hours
- Fuel type used
- Oil change date/hours
- Filter and spark plug service
- Any issues observed (hard start, surging, alarms)
Calendar reminders
Set repeating reminders for monthly exercise, annual oil service, and battery replacement planning. For standby units, also set a reminder to verify controller time/date after daylight saving changes or extended utility outages.
Quick-reference readiness checklist (printable)
BACKUP POWER READINESS (Monthly / Seasonal) Date: ____________ Initials: _____ PORTABLE / STANDBY: ________ Model: ____________ Serial: ____________ HOURS: ________ MONTHLY: [ ] Visual inspection (leaks, debris, damage) [ ] Battery maintainer/charger status OK [ ] Exercise run completed (15–30 min) [ ] Moderate load applied during run (portable) [ ] Controller shows no alarms (standby) FUEL: [ ] Fuel supply adequate for season [ ] Gasoline treated with stabilizer / rotated [ ] Carb drained or run dry after last use (portable) [ ] Propane tank level checked; fittings/hoses inspected LOAD TEST (Quarterly/Semiannual): [ ] Step-load test performed; voltage stable [ ] Notes recorded: __________________________________________ SPARES ON HAND: [ ] Correct oil (qty: ___) [ ] Oil filter(s) [ ] Air filter(s) [ ] Spark plug(s) [ ] Funnel/drain pan/rags [ ] Basic tools CONNECTION GEAR: [ ] Properly rated cord(s) inspected [ ] Inlet box cover seals; no corrosion [ ] Transfer equipment labels intact [ ] Printed operating steps posted near panel